Home battery in the garage, utility room, loft or outside?
Updated 20 October 2026 · SEO Dons Editorial
Which locations does PAS 63100 prefer?
This guide follows on from where a home battery should go under PAS 63100, which lists the places the standard rules out. Here the focus is the four places most homeowners actually consider, and the extra conditions each one brings.
PAS 63100:2024 is a BSI specification on fire protection for home battery systems, sponsored by the Department for Energy Security and Net Zero, and it came into effect on 31 March 2024. MCS has said it has no current standing in UK regulations such as the Building Regulations. But the IET Code of Practice for Electrical Energy Storage Systems, 3rd edition, says that for battery location PAS 63100 should be used, and the MCS battery standard, MIS 3012, refers installers to the latest edition of that Code.
The starting point is simple: where practicable, batteries should be installed outdoors. Only where that is not practicable may they go indoors, and then only in a location that is not excluded, that is ventilated, and that has fire separation where required. A detached outbuilding not intended for habitation counts as outdoors, as does one separated from the house by a main wall rated REI 120.
| Location | How PAS 63100 treats it | Extra conditions | Total stored energy limit per house |
|---|---|---|---|
| Outside wall or ground-mounted | Preferred where practicable | Wall fire performance kept; at least 1 m from escape routes, doors, windows and ventilation ports | 80 kWh |
| Detached garage or outbuilding | Treated as outdoors if not intended for habitation | Impact protection inside a garage | 80 kWh |
| Attached garage | Indoor location unless separated by an REI 120 main wall | Ventilation to outdoors, fire separation, impact protection | 80 kWh with REI 60 separation, otherwise 40 kWh |
| Utility room or plant cupboard | Indoor location | Ventilation to outdoors, fire separation, smoke detection if rarely visited | 40 kWh |
| Loft, roof space or void | Not permitted | Not applicable | Not applicable |
One more limit applies everywhere: the energy stored in a single battery enclosure must not exceed 20 kWh.
Can a home battery go in the garage?
Often, yes, but attached and detached garages are treated differently. A detached garage that is not intended for habitation counts as outdoors. An attached garage counts as an indoor location unless the wall between it and the house meets REI 120, and the indoor rules then apply:
- Ventilation. Any indoor space with a battery must have fresh-air ventilation to outdoors, and the outside edge of that vent must be at least 1 m from doors, windows and other ventilation openings.
- Fire separation. The space needs walls, ceilings and floors rated at least REI 30 between it and the excluded parts of the house, such as bedrooms and unprotected escape routes.
- Storage limit. Up to 80 kWh in total is allowed in a detached garage, or in an attached garage whose fire separation reaches REI 60. Otherwise the limit is 40 kWh.
Garages bring two risks of their own. The first is vehicles: PAS 63100 lists garages, and spots next to driveways, among the locations where batteries need IK10 impact protection or an equivalent such as an impact barrier, and the MIS 3012 checklist asks whether equipment is placed to minimise the risk of vehicle impact. The second is what else is stored there, because a battery must not be installed within 2 m of stored flammable materials or fuel tanks and cylinders. MIS 3012 adds that batteries must not be exposed to submersion in foreseeable flooding, which is worth checking for a garage at the bottom of a slope.
What about a utility room or cupboard?
A utility room or dedicated plant cupboard is an indoor location, so it must meet the same ventilation and REI 30 separation rules as an attached garage, with a 40 kWh limit on total storage. It also has to avoid the excluded spaces. PAS 63100 rules out rooms where people sleep, storage cupboards or spaces that open into those rooms, escape routes that are not protected escape routes (including landings, staircases and corridors), and the corridors, stairs and lobbies of protected escape routes.
Smoke detection is the other key point. Where a battery is in a part of the home that is infrequently visited, such as a store cupboard, PAS 63100 requires a smoke or multi-sensor detector in that location, interlinked with the fire alarm system in the rest of the home and meeting BS 5839-6. Its notes add that a home with a battery system should have a fire detection and alarm system of at least Grade D2, Category LD2, which may mean upgrading an existing system. MIS 3012 makes a similar point for batteries or inverters in rarely visited parts of a building.
The standard also notes that air tightness requirements might rule out batteries in habitable parts of a dwelling, so it is worth asking early whether the room you have in mind counts as a habitable part of the home.
Why can't the battery go in the loft?
PAS 63100 lists voids, roof spaces and lofts among the places a battery must not be installed, alongside cellars or basements with no access to the outside. MCS's own update on the standard confirms that it covers the location of battery storage in a loft space.
The rule is about the battery, not every box in the system. PAS 63100 accepts that power conversion equipment, such as an inverter, may sit in a loft, store cupboard or other rarely visited place, provided a smoke or multi-sensor detector is fitted there and interlinked with the rest of the home. So a design with the inverter in the loft and the battery in the garage can comply, as long as the loft gets its detector.
What does an outside wall installation need?
Outdoors is the preferred option, but the wall itself has to be protected. PAS 63100 says a battery fixed to an external wall must not compromise the wall's fire performance. Cables passing through the wall must be properly fire-stopped, combustible material inside must not be exposed by the installation, and where there is a cavity, cavity barriers must be provided for the services passing through.
Position matters as much as fixing. A wall-mounted or ground-mounted battery must not be within 1 m of escape routes, doors, windows or ventilation openings. If it sits beside a driveway or on a wall adjoining a public highway, PAS 63100 calls for IK10 impact protection. The standard also notes that equipment on an external wall could, in some cases, need planning consent or building control notification, so ask who will check that.
Weight is the final check. MIS 3012 says components must be mounted on surfaces that are structurally sound and can carry their weight, taking point loads into account, and that a qualified structural engineer must be consulted if there is any doubt. Where a wall or floor needs strengthening, responsibility for that work must be set out in the contract.
What should an installer check before choosing the spot?
Under MIS 3012, a certified installer must site the battery so escape routes are not blocked, give the location enough ventilation to prevent overheating while charging, and leave room for installation, commissioning and maintenance to be done safely, including any lifting. After installation, PAS 63100 requires a notice showing a battery is present at the origin of the electrical installation, at the meter position if it is separate, and at the consumer unit the inverter feeds.
Two more questions are worth asking. First, is the company certified for batteries as well as solar? MIS 3002 says that where a quote shows self-consumption with battery storage, it must make clear if the installer is not certified to MIS 3012. Second, will the network operator need to approve the system? MCS notes that adding a battery to solar usually takes total generation above 16 amps per phase, so G99 applies; the process is set out in G98 vs G99 explained.
The solar battery installation guide covers how a battery connects to a solar system, from AC or DC coupling to installation day. Government cost figures leave batteries out, so the solar panel installation cost guide prices the panels and a battery is quoted on top. If you already know where a battery could go in your home, you can send your details through the form below (we reply by email), and ask any installer who quotes to confirm the proposed location against PAS 63100 in writing. If the panels are not fitted yet either, see solar panel and battery installation. Comparing those written answers is the quickest way to see which battery installation proposal has been designed around your home rather than the easiest cable run.
Sources
- BSI, PAS 63100:2024 Electrical installations: Protection against fire of battery energy storage systems for use in dwellings: Specification (published March 2024), checked 20 October 2026.
- BSI Knowledge, PAS 63100:2024 product page, checked 20 October 2026.
- MCS, Update on PAS 63100 and IET Code of Practice 3rd Edition (9 May 2024), checked 20 October 2026.
- MCS, MIS 3012 The Battery Standard (Installation), Issue 1.0, checked 20 October 2026.
- MCS, MIS 3002 The Solar PV Standard (Installation), Issue 6.0 (18 March 2026), checked 20 October 2026.
- MCS, Notifying DNOs, checked 20 October 2026.
Common questions
How much battery storage can a house have under PAS 63100?
No single battery enclosure may hold more than 20 kWh. Across the whole house, the limit is 80 kWh where batteries are outdoors, in a detached garage or outbuilding, or in an attached garage with REI 60 fire separation, and 40 kWh in every other case.
Does a battery in the garage need a smoke alarm?
PAS 63100 requires an interlinked smoke or multi-sensor detector wherever a battery is in an infrequently visited location, and its notes say any home with a battery system should have at least a Grade D2, Category LD2 fire alarm system. Ask the installer how detection will cover the garage you have chosen.
Can the inverter go in the loft if the battery cannot?
Yes. PAS 63100 allows power conversion equipment such as an inverter in a loft or other rarely visited space, provided a smoke or multi-sensor detector is fitted there and interlinked with the fire alarm system in the rest of the home.
Does PAS 63100 apply to large houses?
Its scope excludes dwellings with more than 200 square metres of floor area. The standard notes its fire safety principles can still be applied to larger homes, but recommends consulting a fire safety expert.