Solar PV wiring and isolators: what a home installation should include
Updated 23 October 2026 · SEO Dons Editorial
Which wiring standard applies to a home solar system?
BS 7671, the IET Wiring Regulations, is the UK's national standard for the design, erection and verification of electrical installations, and its Section 712 covers solar PV. It bites in law through two routes. Requirement P1 of the Building Regulations asks for reasonable provision in the design and installation of electrical installations, and regulation 22 of the Electricity Safety, Quality and Continuity Regulations 2002 says a source of energy connected in parallel with the network, where it is part of a low voltage installation, must comply with British Standard Requirements.
The edition has just changed. BSI's article of 15 April 2026 reports Amendment 4 (BS 7671:2018+A4:2026) and says the previous version would be withdrawn on 15 October 2026, a date that has now passed. The IET articles quoted below cite regulation numbers from earlier editions, so check which edition a certificate names and confirm any clause number against it.
What should the DC cable and connectors be like?
UK solar inverters are predominantly transformerless with an unearthed DC side, and the IET says the protective measure is double or reinforced insulation. In practice that means cable made for the job: the IET points to BS EN 50618, which describes cables for the DC side of photovoltaic systems. Regulation 712.521.101, as the IET quotes it, calls for single-core cables with a non-metallic sheath, or single-core conductors in individually insulated conduit or trunking, and says cable must not be placed directly on the surface of the roof. The IET's Code of Practice advises against burying DC cable in walls and asks for a plan of cable locations where burial cannot be avoided, and cable inside the building may need to be of limited smoke production.
Armoured cable is a flag. The IET says steel wire armoured cable made to BS 5467, BS 6724 or BS 7846 does not meet the double insulation requirement because the cores are not double insulated from each other. If a quote or certificate lists armoured DC cable, ask which regulation the designer relies on.
The Fire Protection Association lists water ingress at DC and AC connectors, and poor quality or incompatible components, among the causes of solar fires. Ask which connectors were used, who fitted them and how the joints are kept out of the rain. The wider evidence is in the fire-risk post.
What does a DC isolator need to be?
The IET says inverters need a means of isolation on both the AC and DC side, and that incorrectly rated or poorly installed DC switch-disconnectors are a major contributor to PV-related fires in the UK. The rating is the point. A panel's output is declared under standard test conditions, and the IET says those figures first have to be corrected to a worst-case value before equipment is specified. Rating from the label figures instead could make the device fail when switched under load, which the IET says could be catastrophic.
The device should conform to BS EN IEC 60947-3, and the utilization category is marked on it. The IET summarises the three PV categories:
| Marking | IET guidance |
|---|---|
| DC-PV0 | Not suitable for isolating an inverter where breaking capability is required. A disconnector, not rated for making or breaking current. |
| DC-PV1 | Can be suitable where there are no parallel strings. |
| DC-PV2 | Appropriate when multiple strings are connected in parallel. |
BRE has recorded reports of AC isolator switches being used by mistake in DC circuits, building up heat in the enclosure and causing a fire, so an AC-only switch on the roof side is a fault. Outdoors, the IET notes that bottom entry glands can limit water ingress and that a unit on a south-facing wall sees higher temperatures and UV exposure. It also notes that a circuit-breaker suitable for isolation may be used instead of a switch-disconnector.
What belongs at the consumer unit end?
The existing installation. Regulation 132.16, quoted by the IET, says no addition or alteration should be made until it has been ascertained that the existing equipment, including the distributor's, is adequate, and that the earthing and bonding arrangements must be adequate. Ask what was checked at the consumer unit and the earthing before the inverter was connected.
RCDs. The IET says RCDs are not required for PV systems per se, but may be needed for other reasons, such as fault protection on TT systems or where the AC supply cable is buried in a wall. Where one is used it must switch all live conductors including the neutral, and Regulation 712.531.3.5.1 calls for Type B unless the inverter or installation provides at least simple separation or the manufacturer says Type B is not needed. Unidirectional protective devices are not suitable.
Surge protection. Unless a regulation or a lightning protection system requires it, the IET says the decision to fit surge protective devices rests with the owner, who should be given enough information to decide. Ask whether that conversation happened and was recorded.
Which labels and instructions should be left behind?
The IET lists "Solar PV in installation" and other notices required by Regulation 712.514, warning notices for alternative supplies under Regulation 514.15, and clear marking of isolators and protective devices to show what they serve. For the user, it says brief start-up and shutdown procedures, an emergency shutdown procedure and the meaning of main indications and fault codes should be provided.
What should you compare with the electrical installation certificate?
| Check | What the certificate and handover should show |
|---|---|
| Edition | The edition of BS 7671 worked to. For new work, A4:2026. |
| DC cable | Cable type for the DC side, non-metallic sheath, kept off the roof surface. |
| DC isolator | BS EN IEC 60947-3 marking, a DC-PV category that suits the strings, rated from corrected maximum values. |
| AC side | Isolation on the AC side, and RCD type and neutral switching if an RCD is fitted. |
| Existing installation | A record that the consumer unit, earthing and bonding were checked. |
| Surge protection | The owner's decision recorded. |
| Labels and user instructions | Notices fitted, shutdown procedure supplied. |
| Maintenance | A check interval. The IET says PV systems are not fit-and-forget. |
The parts these checks refer to are laid out in how solar panels work on a house, and the paperwork that sits around the certificate is in solar panels and building regulations. A quote that states these specifications is easier to compare, and the cost guide explains how they feed into the price. Readers can send an enquiry through the form on this site.
Sources
- Solar photovoltaic DC switch-disconnector selection and configuration (Wiring Matters 109), IET, April 2026, checked 22 October 2026
- Exploring wiring systems for unearthed DC solar PV systems, part 1 (Wiring Matters 104), IET, March 2025, checked 22 October 2026
- Bidirectional protective devices (Wiring Matters 99), IET, March 2024, checked 22 October 2026
- User and maintenance instructions for modern domestic electrical installations (Wiring Matters 105), IET, May 2025, checked 22 October 2026
- Surge protective devices (Wiring Matters 98), IET, November 2023, checked 22 October 2026
- BS 7671:2018+A4:2026: get the latest amendment, BSI, 15 April 2026, checked 22 October 2026
- Solar panel systems and fire safety, BRE Group, 11 November 2013, checked 22 October 2026
- Are solar panels a fire hazard?, Fire Protection Association, 22 February 2024, checked 22 October 2026
- Building Regulations 2010, Schedule 1, legislation.gov.uk, checked 22 October 2026
- Electricity Safety, Quality and Continuity Regulations 2002, regulation 22, legislation.gov.uk, checked 22 October 2026
Common questions
Does every system need a DC isolator?
The IET says inverters require a means of isolation from both the AC and DC side. That can be a DC switch-disconnector, or a circuit-breaker suitable for isolation under Regulation 712.537.2.2.102. What matters is that it is rated for the array and marked for DC use.
Is the DC side of a solar system earthed?
Usually not. The IET says UK inverters are predominantly transformerless with an unearthed DC side, and Regulation 712.312.2 does not permit earthing one DC live conductor unless there is at least simple separation between AC and DC. The protection is double or reinforced insulation.
How often should the isolator and connections be checked?
The IET says the BS EN 62446 series recommends inspection and testing intervals no greater than those for the AC system. A minimum inspection includes terminal torque, conductors suited to the terminals and cycling the device off-load. It also says lack of maintenance is a contributing factor to PV fires in the UK.